CS-2M Container Energy Storage – Operation Guide

Documentation/Operation

CS-2M Container Energy Storage – Operation Guide

OperationVersion V1.0Updated 2026-10-20

This guide explains daily start-up, operation and shutdown of the EVX CS-2M 2 MWh container energy storage system.

Before start-up

  • Confirm the fire suppression system is normal.
  • Check coolant level and pressure.
  • Verify EMS and PCS communication.

Start-up

  1. Close the auxiliary power switch.
  2. Start the BMS and wait for self-test.
  3. Start the PCS and enter standby.
  4. Select the operating strategy in the EMS.

Daily operation

Check system efficiency, cell temperature and SOC every hour. Stop the system immediately on a level-1 alarm and contact service.

Shutdown

  1. Stop charging/discharging in the EMS.
  2. Switch the PCS to stopped state.
  3. Open the auxiliary power switch.

Notes

  • Never plug or unplug HV connectors under load.
  • No flammable materials inside the container.
  • Apply lockout/tagout before maintenance.